Skip to main content
Loading…
This section is included in your selections.

The following local amendments to Chapter 6 of the International Fire Code, entitled “Building Services and Systems,” are hereby adopted and incorporated into the International Fire Code as if fully set forth therein:

(1) Section 605 of the International Fire Code is amended by substituting subsection 605.6 with the following:

605.6. Testing of equipment. Refrigeration equipment and systems having a refrigerant circuit more than 220 pounds of Group A1 or 30 pounds of any other group refrigerant shall be subject to periodic testing in accordance with Section 605.6.1. A written record of the required testing shall be maintained on the premises for a minimum of three years; a copy shall be submitted by an approved means to the fire code official within 30 calendar days of the testing; and a label or tag shall be affixed to the individual system identifying the date of the testing. Tests of emergency devices or systems required by this chapter shall be conducted by persons trained and qualified in refrigeration systems.

(2) Section 607 of the International Fire Code is amended by supplementing subsection 607.2 with the following two subsections:

607.2.2. Permit Required. Permits shall be required as set forth in Section 105.6.

607.2.3. Approved drawing. The stamped and approved cook line drawing shall be displayed adjacent to the suppression system pull station prior to the final inspection.

(3) Section 607 of the International Fire Code is amended by substituting subsection 607.3.3.3 with the following:

607.3.3.3. Records. Records for inspections shall state the individual and company performing the inspection, a description of the inspection and when the inspection took place. Records for cleanings shall state the individual and company performing the cleaning and when the cleaning took place. Such records shall be completed after each inspection or cleaning, maintained on the premises for a minimum of three years; a copy shall be sent to the fire code official within 30 days of the inspection or cleaning.

(Ord. 19-20 § 3 (Exh. 2); Ord. 02-19 § 1 (Exh. A); Ord. 11-16 § 2 (Exh. 2); Ord. 03-13 § 2 (Exh. 2); Ord. 05-10 § 2 (Exh. 2). Formerly 15.20.050)