Skip to main content
Loading…
This section is included in your selections.

The following local amendments to Chapter 9 of the International Fire Code, entitled “Fire Protection Systems,” are hereby adopted and incorporated into the International Fire Code as if fully set forth therein:

(1) Section 901 of the International Fire Code is amended by substituting subsection 901.6.3 with the following:

901.6.3. Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for three years; a copy shall be submitted by an approved means to the fire code official within 30 calendar days of each test, inspection, or maintenance of the system; and a label or tag shall be affixed to the individual system identifying the date of the scheduled confidence test.

(2) Section 901 of the International Fire Code is amended by adding new subsection 901.11 as follows:

901.11. Emergency contacts. It shall be the responsibility of the owner of any monitored fire protection system to provide and maintain a minimum of three emergency contacts that are capable of responding to the system location with their monitoring company.

(3) Section 902 of the International Fire Code is amended by adding the following to the list in subsection 902.1:

PROBLEMATIC FIRE PROTECTION SYSTEM.

(4) Section 903 of the International Fire Code is amended by substituting subsection 903.2 with the following:

903.2 Where required. An automatic sprinkler system shall be provided for when one of the following conditions exist:

1. In all buildings without adequate fire flow as required by this code.

Exception: Miscellaneous Group U Occupancies.

2. All new buildings and structures regulated by the International Building Code requiring 2,000 gallons per minute or more fire flow, or with a gross floor area of 10,000 or more square feet (929 m2), or where this code provides a more restrictive floor/fire area requirement, and shall be provided in all locations or where described by this code.

Exception: Spaces or areas in telecommunications buildings used exclusively for telecommunications equipment, associated electrical power distribution equipment, batteries, and standby engines, provided those spaces or areas are equipped throughout with an automatic smoke detection system in accordance with Section 907.2 and are separated from the remainder of the building by not less than 1 hour fire barriers constructed in accordance with Section 707 of the International Building Code or not less than 2 hour horizontal assemblies constructed in accordance with Section 712 of the International Building Code, or both.

3. Where this code requires the installation of an automatic sprinkler system to protect an occupancy within an otherwise non-sprinklered building, then automatic sprinkler protection will be required throughout the entire building.

4. When the required fire apparatus access roadway grade is 12 percent or greater.

5. Without approved fire department access as defined in the Covington Design and Construction Standards.

(5) Section 903 of the International Fire Code is amended by adding new subsection 903.2.9.3 as follows:

903.2.9.3 Speculative use warehouses. Where the occupant, tenant, or use of the building or storage commodity has not been determined or it is otherwise a speculative use warehouse or building, the automatic sprinkler system shall be designed to protect not less than Class IV non-encapsulated commodities on wood pallets, with no solid, slatted, or wire mesh shelving, and with aisles that are 8 feet or more in width and up to 20 feet in height.

(6) Section 903 of the International Fire Code is amended by adding new subsection 903.3.9 as follows:

903.3.9. Check valve. All automatic sprinkler system risers shall be equipped with a check valve.

(7) Section 903 of the International Fire Code is amended by adding new subsection 903.7 as follows:

903.7 Riser Room Access. All risers shall be located in a dedicated room with an exterior door, interior lighting and heat.

(8) Section 907 of the International Fire Code is amended by substituting subsection 907.1.3 with the following:

907.1.3 Equipment. Systems and their components shall be listed and approved for the purpose for which they are installed. All new alarm systems shall be addressable. Each device shall have its own address and shall annunciate individual addresses at a UL Central Station.

(9) Section 907 of the International Fire Code is amended by substituting subsection 907.6.3 with the following:

907.6.3 Initiating device identification. The fire alarm system shall identify the specific initiating device address, location, device type, floor level where applicable and status including indication of normal, alarm, trouble and supervisory status, as appropriate.

Exception: Special initiating devices that do not support individual device identification.

(10) Section 907 of the International Fire Code is amended by adding new subsection 907.8.5.1 as follows:

907.8.5.1. Records. Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for three years; a copy shall be submitted by an approved means to the fire code official within 30 calendar days of each test, inspection, or maintenance of the system; and a label or tag shall be affixed to the individual system identifying the date of the scheduled confidence test.

(11) Section 907 of the International Fire Code is amended by adding new subsection 907.12 as follows:

907.12. Latched alarms. All signals shall be automatically “latched” at the alarm panel until their operated devices are returned to normal condition, and the alarm panel is manually reset.

(12) Section 907 of the International Fire Code is amended by adding new subsection 907.13 as follows:

907.13 Resetting. All fire alarm panels shall be reset only by an approved person.

907.13.1. Reset Code. The reset code for the fire alarm panel or keypad shall be 3-7-1-2-3-4. The reset code shall not be changed without approval of the fire code official.

(13) Section 907 of the International Fire Code is amended by adding new subsection 907.14 as follows:

907.14 Fire Alarm Control Panel. All fire alarm control panels shall be located in the riser room designed and installed in accordance with Section 903.7 or an approved location.

(14) Section 909 of the International Fire Code is amended by substituting subsection 909.20.2 with the following:

909.20.2 Written record. The records shall include the date of the maintenance, identification of the servicing personnel and notification of any unsatisfactory condition and the corrective action taken, including parts replacement. The written record of smoke control system testing and maintenance shall be maintained on the premises for three years; a copy shall be submitted by an approved means to the fire code official within 30 days of each test or maintenance of the system; and a label or tag shall be affixed to the individual system identifying the date of the scheduled testing.

(15) Section 912 of the International Fire Code is amended by substituting subsection 912.5 with the following:

912.5 Signs. Fire department connections shall be clearly identified in an approved manner.

All fire department connections shall have an approved sign attached below the Siamese clapper. The sign shall specify the type of water-based fire protection system, the structure, and the building areas served.

(Ord. 19-20 § 3 (Exh. 2); Ord. 02-19 § 1 (Exh. A); Ord. 11-16 § 2 (Exh. 2); Ord. 03-13 § 2 (Exh. 2); Ord. 05-10 § 2 (Exh. 2). Formerly 15.20.070)